Rules pipes
Below is the list of rules implemented by C3DRENESG for the pipes.
To edit these values in your project, use the command use the command
CEDITRULES.
If you've used the previous version (version C3DRENESG4 C3DRENESG2 or 2736 or
above), use the command
UPDATERULES, so that the rules are converted to this new version.
-
Cover - Limits the maximum and minimum cover above the pipe.
Use to classify the type of pipe with simple frame or reinforced by example
Accepts:
-
Maximum Cover
-
Minimum Cover
-
water height - Limits the water height flow.
Drain pipes and sewer work blends with the free section, ie without load.
Accepts:
-
Pipe drop - Applies to sewer pipes.
Step or fall above a certain value is added in the down-pipe
connection with the PV
Accepts:
Step
-
Max.
All pipes rung above this value will be marked
to have down-pipe.
-
Slope - Limits the pipe slope.
High slopes entail high speeds, wearing pipe.
Low slopes, causing low speeds and sedimentation.
Accepts:
-
Maximum Slope
-
Minimum Slope
-
Length - Limits the length of the pipe.
Typically utilities define the maximum length of a stretch as one compatible device cleaning.
Accepts:
-
Maximum length
-
Minimum length
-
Trench width - Limits the width of the bottom of the trench to lay the pipe.
The minimum value must be greater than the width of the outer pipe.
Accepts:
-
Maximum width
-
Minimum width
Use values compatible with the equipment used in the excavation of the trench.
-
speed - Limits the flow velocity.
Some agencies limit the maximum speed at 4.5 m/s, other 5 m/s.
Accepts:
-
Maximum Speed
-
Minimum Speed
See also structures rules